Change Over Switch
LW26-63/LW26-63F M-O-G
Application
The LW26 series rotary switch mainly applies to 440V and below, AC 50Hz or
240V and below DC circuits. For breaking and closing, change-over of circuits under infrequently manual operation. And the typical application are: control switch of 3 phase motors, control switch of switch gear, control switch of instruments, and change-over switch of machinery and welding machine.
The series comply with the GB 14048.3, GB 14048.5 and IEC 60947-3,IEC 60947-5-1. The LW26 series have 8 current ratings: 10A, 20A, 25A, 32A, 40A, 63A( 125A, 160A,250A, and 315A. They were designed for multiple functions, wide variety of applications.The LW26-10; LW26-20, LW26-25, LW26-32F, LW26-40F and LW26-63F have finger protection terminals.
The LW26 series rotary switch has two derivatives: LW26GS Pad-lock type and LW26SKey-lock type. Both of them are applicable in circuits when an physical control is required.
Working Conditions
(1) Ambient temperature DO NOT exceed 40℃. and the average temperature, measured over a period of 24 hours. DO NOT exceed 35℃.
(2) Ambient temperature should not be below -25℃.
(3) Should not be installed above 2000m above sea level.
(4) The humidity should not exceed 50% when the ambient temperature is 40℃ and higher humidity is allowed for lower temperature.
Technical Parameters LW26-63/LW26-63F
Rated Insulation Voltage (Ui V) | 660/690 |
Rated Thermal Current (Ith A) | 63 |
Rated Working Voltage (Ue V) | 240 440 |
Rated Working Current (le) | |
AC-21A AC-22A A | 63 63 |
AC-23A A | 57 57 |
AC-2 A | 57 57 |
AC-3 A | 36 36 |
AC-4 A | 15 15 |
Rated Power (P) | |
AC-23A KW | 15/10 30/18.5 |
AC-2 KW | 18.5 30 |
AC-3 KW | 11/6 18.5/11 |
AC-4 KW | 5.5/2.4 7.5/4 |
Re1: Neutral
Re2: The power under: AC-23 A, AC-3,AC-4 are in three phase three poles, and the denominator represents the power under single phase two poles.
Mechanical Life
Mechanical life without load: 0.1x106 times, operation frequency is 120 times/h
Mechanical life with load: 0.03x106 times operation frequency is 120 times/h
Dimensions and Installation