ADL8-63

Our Products > ADL8-63N > ADL8-63

ADL8-63

ADL8-63N RCBO mainly applies to the circuit of AC 50Hz, rated voltage 240V, rated current up to 63A.

ADL8-63N

RCBO

Construction and Feature

ADL8-63N RCBO mainly applies to the circuit of AC 50Hz, rated voltage 240V, rated current up to 63A. When electric shock occurs to human, leakage current or voltage in grid exceeds stipulated values, RCBO cuts off the fault power in a very short time to protect the safety of human and electrical equipment, it also owns the functions of overload and short circuit protection. In addition, it can switch on and off infrequently the electrical facilities and lighting circuit while the circuit works well.


Main Technical Data

Types

Values

Rated voltage Un

240VAC

Rated current In

6A,10A,16A,20A,25A,32A,40A,50A,63A

Rated residual operated   current lΔn

0.03A,0.1A,0.3A

Rated residual non   tripping current lΔno

0.5 lΔn

Poles

1P+N

 DC component

AC type, A type

Instant   tipping type

B type, C type, D type

Rated short circuit breaking capacity lcn

6000A

Rated residual making and breaking capacity IΔm

500A

Breaking time of residual operated current

See Form 2 and 3

Overcurrent protection properties

See Form 4, Diagram 1 and 2

Mechanical life

10000 Operation Time(time/hour):240

Electrical life

2000 Operation Time(time/hour):120

Connection wire

See Form 5

Tightening torque

1.5N.m

Nominal temperature

30

Operated ambient   temperature

-25+40

Stored ambient   temperature

-25+70

Pollution level

2

Protection level

IP20

Mounting type

 

Breaking time of AC type

Type

ln(A)

IΔn(A)

Breaking time(s) when IΔ equals to the below   values

lΔn

2IΔn

5IΔn

025A,5A~200A,500A

AC

6~40

0.03,0.1,0.3

0.3

0.15

0.04

0.04

 

Breaking time of A type

Type

ln(A)

IΔn(A)

Breaking time(s) when IΔ equals to the below   values

1.4IΔn

2.8IΔn

7IΔn

0.35A

350A

A

6~40

0.03

0.3

0.15


0.04

0.04

0.1,03

0.3

0.15

0.04


0.04


(Overcurrent protection properties(nominal temperature 30
)

Item

Type

Test current

Initial status

Tripping or non tripping time limit

Expected result

Remarks

a

B,C

1.13ln

Cold

t<1h

Non tripping


b


1.45ln

Test following the previous procedure;

Process after test

t<1h

Trip

Current increases to stipulated value within 5s

c


2.55ln

Cold

1s<t<60s(In32A)

1s<t<120s(ln>32A)

Trip


d

B

C

3ln

5ln

Cold

t<0.1s

Non tripping

Connection of current by opening auxiliary switch

e

B

C

5ln

10ln

Cold

t<0.1s

Trip

Connection of current by opening auxiliary switch



Characteristic Curve







Connection wire

Rated current ln(A)

 

Section area of copper wire S(mm2)

6

1.0

10

1.5

16,20

2.5

25

4

32

6

40

10

50

13

63

15


Overall and mounting sizes(mm)

Previous: ADL9-40